Għażla tal-proporzjon tat-transformer tal-kurrent sekwenza żero

Dec 13, 2023|

1. Protezzjoni eżistenti issettjar valur għażla ħin li jvarjaw proporzjon

B'settings ta 'protezzjoni diġà fis-seħħ, il-proporzjon ta' trasformazzjoni huwa faċli biex tagħżel.

Jekk il-valur tal-issettjar huwa l-azzjoni ta 'protezzjoni meta l-kurrent primarju huwa 80A, agħżel 100/5 jew 100/1 bħala l-istandard nazzjonali affidabbli.

2. Għażla tal-proporzjon tat-trasformazzjoni tas-sistema tal-ert tar-reżistenza

Il-kurrent tal-punt tal-ert ta 'sistema tal-ert tar-reżistenza jikkonsisti f'żewġ komponenti, wieħed huwa l-kurrent kapaċitattiv u l-ieħor huwa l-kurrent tar-reżistenza tal-punt newtrali, u d-differenza bejn it-tnejn hija 90o. Il-kurrent ta 'sekwenza żero taċ-ċirkwit tal-ħsara huwa ugwali għad-differenza bejn il-kurrent tal-punt tal-art u l-vettur tal-kurrent tal-kapaċità tal-art tal-linja, jiġifieri, huwa ugwali għall-valur negattiv tas-somma tal-kurrent tal-kapaċità tal-art u l-kurrent resistiv vettur tal-linji kollha mhux ta' ħsara. Bħal: sistema ta' ertjar tar-reżistenza (IR=1-1.5IC).

Huwa rakkomandat li tagħżel il-proporzjon tat-transformer tal-kurrent sekwenza żero: 50/1 100/1 150/1 200/1 100/5 200/5.

3. Għażla tal-proporzjon tat-transformer tal-kurrent ta 'sekwenza żero għal sistemi ta' coil ta 'soppressjoni ta' ark mhux ertjat u punt newtrali ertjat

When the grounding current of this system is large, or when the minimum starting current of the protection is small, a zero-sequence current transformer with a larger transformation ratio can be used, such as 50/1, 100/1, 100/5, 150/5 and above. However, some systems with ungrounded neutral points generally do not allow the grounding current to exceed 10A, so protection below 10A is generally required. In the arc suppression coil grounding system, due to the neutralization of the inductor current and the capacitor current, there will generally be no ground current exceeding 10A (generally overcompensation, the actual ground current is already the inductor current) due to the use of comprehensive protection (without comprehensive protection) Sometimes high-sensitivity zero-sequence current transformers and their matching relays are used, see 2). It requires a setting value. Generally, the setting value is ≤10A. If the setting value of the primary current is 5A, 100/5A or 20/1A can be considered. When the primary current is 5A, the secondary current is 0.25A, which generally exceeds the starting current of the comprehensive protection. If the minimum starting current of comprehensive protection is >0.25A, għandek tagħżel il-proporzjonijiet ta 'trasformazzjoni ta' 75/5, 50/5, 15/1, u 10/1. Huwa aħjar li tuża transformers tal-kurrent ta 'sekwenza żero integrali b'dawn il-proporzjonijiet, inkella l-eżattezza titnaqqas. Agħar.

4. Għażla tal-proporzjon ta 'trasformazzjoni għal sistema ta' ertjar ta 'kurrent għoli

Atterrar b'fażi waħda ta 'sistema ta' ertjar punt newtrali huwa short circuit ta 'fażi waħda. Tista 'tagħżel proporzjon ta' trasformazzjoni akbar, bħal proporzjon ta 'trasformazzjoni 'l fuq minn 150/5 jew 150/1. M'għandux ikun żgħir wisq, inkella ma tkunx tista 'tevita kurrent żbilanċjat. Innota li l-linja newtrali (N) ma taqsamx CT.